Communication Description IM/265/7/9/ADD/FF-EN_01 Series 2600T Pressure TransmittersConnection to FOUNDATION Fieldbus For pressure, differential
Device Introduction 10 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01
Device Introduction IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 11 - DEVICE Model: 2600T Series- Models 267 / 269 Type: Multivari
Device Introduction 12 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01
Hardware Characteristics IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 13 5 Hardware Characteristics 5.1 Current limitation This
Hardware Characteristics 14 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 5.3 Local Keys Three external push buttons are availabl
Hardware Characteristics IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 15 5.4 Structure tree The menu is called up using the mode
Hardware Characteristics 16 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Main menu Submenu (other parameters / explanations)
Network Architecture IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 17 6 Network Architecture A simple generic FOUNDATIONTM Fieldbus
Network Architecture 18 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 M00506Trunk & Spurs Daisy Chain TreeJunction Box Fig. 4: F
Network Architecture IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 19 The models 265 / 267 / 269 FF have the following power requireme
Blinder Text 2 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Series 2600T Pressure Transmitters Connection to FOUNDATION Fieldbus
Network Architecture 20 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 6.1 Electrical Connections The 2600 FF is a Bus Powered dev
FOUNDATION Fieldbus Overview IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 21 Approvals 7 FOUNDATION Fieldbus Overview In the Fig.
FOUNDATION Fieldbus Overview 22 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 In the Fig. 8 is represented the macro cycle of the abo
Initialisation IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 23 8 Initialisation At the power up, the 2600T FF executes some inter
Device Addressing 24 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 A 9 Device Addressing When the models 265 / 267 / 269 FF Transmi
Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 25 K 10 Device Configuration 10.1 Device Description The model
Device Configuration 26 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 10.2 Resource Block Idx Name Byte PC Description 0 BLO
Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 27 Idx Name Byte PC Description 1 R/W Grant 14 GRANT_DENY 1
Device Configuration 28 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description 26 SHED_RCAS 4 R/W Time du
Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 29 Idx Name Byte PC Description The alert status associated to
Preamble IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 3 1 Preamble ...
Device Configuration 30 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description 46 DIAGNOSIS 4 R Diagnosis
Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 31 Idx Name Byte PC Description 48 DIAGNOSIS_ EXTENSION2 2 R
Device Configuration 32 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 10.3 Analog Input Function Block Idx Name Byte PC Descr
Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 33 Idx Name Byte PC Description 4 R/W High Range 4 R/W Low Rang
Device Configuration 34 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description Code for Flow 1347 cubic me
Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 35 Idx Name Byte PC Description Code for Volume 1034 cubic
Device Configuration 36 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description 17 LOW_CUT 4 R/W Limit use
Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 37 Idx Name Byte PC Description The block alarm is used for a
Device Configuration 38 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description The HI HI Alarm data 1 R/W U
Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 39 10.4 Pressure Transducer Block The modification of the flow
Preamble 4 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 1 Preamble In order to make easier the description, all the variables menti
Device Configuration 40 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description The block alarm is used for
Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 41 Idx Name Byte PC Description 4 R This is the output value
Device Configuration 42 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description 26 SENS_CAL_WHO 32 R/W The
Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 43 Idx Name Byte PC Description Type of Process connection: 36
Device Configuration 44 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description Number of remote seals: 40 NUM
Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 45 Idx Name Byte PC Description Linearization type: 51 LIN_TYPE
Device Configuration 46 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description 58 TAB_OP_CODE 1 58 Modifi
Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 47 Idx Name Byte PC Description 72 UPPER_RANGE_ FAILURE 1 R/W
Device Configuration 48 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 10.5 PID Function Block Idx Name Byte PC Description 0
Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 49 Idx Name Byte PC Description 4 R/W High Range 4 R/W Low Rang
FOUNDATION Fieldbus Definition IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 5 3 FOUNDATION Fieldbus Definition FOUNDATION™ Field
Device Configuration 50 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description 4 R/W Remote set point value
Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 51 Idx Name Byte PC Description 4 R The value required by an
Device Configuration 52 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description 4 R/W This input is used as
Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 53 Idx Name Byte PC Description The summary alarm is used for
Device Configuration 54 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description 58 DV_LO_PRI 1 R/W The Pri
Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 55 Idx Name Byte PC Description Low Low Alarm data 1 R/W Unac
Device Configuration 56 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 10.6 Temperature Transducer Block (only 267 / 269 transmitter
Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 57 Idx Name Byte PC Description The block alarm is used for a
Device Configuration 58 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description 16 CAL_POINT_HI 4 R/W The
Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 59 10.7 Multi Variable Block (only 267C / 269C transmitters) Th
Device Introduction 6 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 4.2 FOUNDATIONTM Fieldbus Version Considerations The models
Device Configuration 60 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description 12 PRESSURE_DEFAULT 4 R Pre
Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 61 Idx Name Byte PC Description 22 SIMULATE_ PRESSURE 1 R/? S
Device Configuration 62 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description The block alarm is used for
Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 63 Idx Name Byte PC Description 36 OUT_MASS_FLOW_ MAX 4 R Max
Operating Modes 64 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 11 Operating Modes As defined by the FOUNDATIONTM Fieldbus specif
Process Flow IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 65 12 Process Flow The following Figures show the possible connections
Process Flow 66 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 M00515BlockPressureTransducer2MVTemp.VOLAnalog1InputTemp.MediumOUTAnalo
Process Flow IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 67 12.2 Custom Pressure Transducer Block M00516Output ScalingSTATIC_PR
Process Flow 68 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 12.4 PID Function Block M00518ScalingwithLimitingwithOUT_HI_LIMOUT_
Process Flow IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 69 12.5 PID algorithm M00519FF_deviationif FF.status(k-1) = GOOD and F
Device Introduction IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 7 - LAS Functionality With this functionality the models 265 / 26
Process Flow 70 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 12.6 Custom Temperature Transducer Block M00520SensorTemperatureTem
Process Flow IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 71 12.8 Troubleshooting Few considerations about the most common wrong
Process Flow 72 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 12.9 Status supported The FOUNDATION™ Fieldbus defines different dy
Process Flow IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 73 Configuration error detail: Set if the AIFB Channel is different by 0 b
Process Flow 74 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Details for UNCERTAIN 68 44 0 1 0 0 0 1 = Last Usable Value TB 72 4
Process Flow IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 75 Details for GOOD (non-cascade) 128 80 1 0 0 0 0 0 = ok TB, AI, MV,
Process Flow 76 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Details for GOOD (cascade) 192 C0 1 1 0 0 0 0 = ok PID 196 C4 1 1
Process Flow IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 77 Details for bits 'LIMITS' +0 +00 0 0 = ok +1 +01
Device Specification Data 78 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 13 Device Specification Data The delivery of the model
Device Specification Data IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 79 The following table is a summary of the most important mod
Device Introduction 8 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 - FMS services supported: - Initiate - Abort - Status - Id
Reference 80 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 K 14 Reference 1. Function Block Application Process – Part 2. n° FF-
ABB has Sales & Customer Support expertise in over 100 countries worldwide. www.abb.com/pressure The Company’s policy is one of continuou
Device Introduction IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 9 4.3 Registration Details - DEVICE Model: 2600T Series- Model