67
UK
081 Relay output OP1
To change the behaviour of relay output OP1 on the alarm
centre PCB:
1. On the control unit, enter:
081
2. The LCD display shows: 081: Bell
3. Via the keypad, select from the following items
and press:
00
Bell
This output is activated at local and
external alarms. Set the siren delay and
duration in menu items 41 and 42.
01
EE Follow
This output is activated if the entry/exit
delay is active. Note that this output is
not activated if the exit mode “internal”
is programmed to “silent” or
“immediate”.
02
Armed Lamp
This output is activated if the alarm
centre is completely or internally
activated.
03
Set Latch
This output is activated if the alarm
centre is completely or internally
activated. The output is also activated if
the alarm centre is reset or if a walk test
is started.
04
Shock sensor reset
This output is activated for 5 seconds at
the start of the exit delay.
05
Walk Test
This output is activated during the user
and programmer walk test. The output
is connected to the walk test input of
the motion sensor.
06
Ready Lamp
This output is activated if the alarm
centre is ready for complete or internal
activation. The alarm centre is ready
even if the zones with the properties
“entry/exit” or “entry to follow” are
opened.
07
24 Hour
This output is activated if a 24-hour
zone triggers an alarm. The output is
deactivated if the alarm centre is
deactivated.
08
Strobe
This output is activated if a local or
external alarm is triggered. The output
remains active until the alarm centre is
deactivated.
09
Smoke Reset
This output is used to reset smoke
detectors. This output is activated for at
least 3 seconds following every
deactivation and reset of the alarm
centre following an alarm.
10
Siren Test
This output is activated following
programming and during a siren test
(command 91 in the program menu).
11
Strobe Set
This output is activated for 10 seconds
after the alarm centre is activated and
the alarm centre is active. The output
can be used to issue an active
acknowledgement.
12
Set 1
This output is activated for a definable
time period (command 170) if the alarm
centre is activated completely (A) or
internally (B), (C) or (D) (command
171).
13
Unset 1
This output is activated for a definable
time period (command 172) if the alarm
centre is deactivated completely (A) or
internally (B), (C) or (D) (command
171).
14
Confirm
This output is active during a confirmed
alarm.
Vista de pagina 170
1 2 ... 166 167 168 169 170 171 172 173 174 175 176 ... 483 484

Comentarios a estos manuales

Sin comentarios

Vision Controls PC/workstation barebones user manuals

The list of Vision Controls PC/workstation barebones products contains 6 user manuals for 1 models. All pdf user’s guides are available for download or viewing online.

Click on an alphabet below to scroll to the full list of models starting with that letter

Models Document Type
Cam SS Version 5.01
User Manual   Vision Controls Cam SS Version 5.01 User manual, 108 pages
Instruction Manual   Vision Controls Cam SS Version 5.01 Instruction manual, 71 pages
User Manual   Vision Controls Cam SS Version 5.01 User manual, 414 pages
User's Guide   Vision Controls Cam SS Version 5.01 User guide, 16 pages
User Manual   Vision Controls Cam SS Version 5.01 User manual, 12 pages
Instruction Manual   Vision Controls Cam SS Version 5.01 Instruction manual, 76 pages