83
Network Error (see note 3)
Tamper Alarm
Unset (see note 1)
Set (see note 1)
Zone Omitted (see note 2)
Medical Alarm
Key Box
The channels are preset as follows:
Channel Setting
1Fire
2 Panic
3 Bur
lar
4 Enabled / Disabled
5 Omit
6 Not Used
7 Not Used
8 Technical
20.1.8 FF Report Restorals
Select whether the restoration of a function (closing of an alarm zone, error clearance)
should be transmitted to the command centre. If this function is disabled, only faults or
alarms are transmitted to the command centre but not the restoration (OK message) of
this function.
20.1.9 SIA Report Mode
Select this, then select the Level of the transmission. The following table details which
events should be transmitted for the SIA 1 report.
Trigger Basic SIA
code
without
zone no. or
user
Sum SIA
code without
zone no. or
user
Middle SIA
code with
zone no.
and user
Complete SIA
code with
zone no.
and user
Medical control panel MA MA MA MA
Social Care QA QA QA QA
Fire FA FA FA FA
Fire control panel FA FA FA FA
Fire control panel OK - FR FR FR
Fire OK - FR FR FR
Panic PA PA PA PA
Panic control panel PA PA PA PA
Panic control panel OK - PR PR PR
Panic OK - PR PR PR
Bur
lar
BA BA BA BA
Burglary OK - - BR BR
Cover tamper contact - TA TA TA
Cover tamper contact OK - - TR TR
Tamper ext. siren - - TA TA
Tamper ext. siren OK - - TR TR
Tamper sensor TA TA TA TA
Tamper sensor OK - - TR TR
Tamper s
stem - TA TA TA
Tamper system OK - - TR TR
Key box open - - BA BA
Key box closed - - BR BR
Technical alarm - UA UA UA
Technical alarm OK - UR UR UR
Power failure - - - AT
Power failure OK - - - AR
Reset - OR OR OR
Battery fault - - - YT
1. Open and close have the same functions as “Open/Close”, but are
made on two separate channels.
2. Zone blocked: The wireless alarm centre sends this signal for five
seconds when the user blocks a zone.
3. The wireless alarm centre either delays the reporting or logging of
network errors, or exits the installation menu with a network error after
15-18 minutes (random selection). In Germany, the wireless alarm
centre waits at least 60 minutes before reporting.